What are the requirements for partitions in isolation rooms?

It is mandatory to have a partition of at least 1.8 metre in height between beds in 2-bedded isolation rooms. The beds should be at least 1 metre apart (lengthwise) and the partition should be non-porous to minimise transmission via respiratory droplets. The partition is necessary even if the beds are farther than 1 metre apart.

The image shows the distance between isolation beds.